Parameter Window - Gx Status - ABB i-bus KNX Product Manual

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.2.3.2.1

Parameter window - Gx Status

In this parameter window, the status response of the selected lighting group is parameterized.
Each lighting group is individual and can be programmed independently of the other lighting groups. The
parameterization relates to the communication objects of the lighting group (Group x).
The status reaction of the whole output, see
of the parameterization of the status response of the lighting group.
Status response of switching state
Options:
No: The status of the switch state is not actively sent on the KNX.
Yes: via object "Switch/Status": The common communication object Switch/Status receives the switch
telegram, and the current status becomes active and is sent on the KNX.
Yes: via separate object "Status switch": An additional Status switch communication object is enabled.
Using it, a 1 bit telegram with the actual switch status is sent on the KNX. This option is not available if
the lighting group is parameterized as a Light controller or Slave.
No
Yes: via object "Switch/Status"
Yes: via separate object "Status Switch"
Parameter window Status -
DLR/S 8.16.1M | 2CDC 507 100 D0202 77
Central, page 61, is independent