Device Technology; Jra/S X.230.5.1 Blind / Roller Shutter Actuator With Travel Detection And Manual Operation, X-Fold, 230 V, Mdrc; Technical Specifications - ABB i-bus KNX Product Manual

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX

Device technology

2
Device technology
2.1
JRA/S X.230.5.1 Blind / Roller Shutter Actuator with Travel Detection and
Manual Operation, x-fold, 230 V, MDRC
JRA/S 8.230.5.1
2.1.1

Technical specifications

Supply
Outputs
Connections
The 2, 4 and 8-fold blind/roller shutter
actuators with automatic travel detection
control 230 V AC drives, acting
independently of one another, to position
blinds, roller shutters, awnings and other
blinds/shutters via ABB i-bus
addition, the devices control, for example,
ventilation flaps, gates and windows. The
travel times of the drives are detected
automatically via end position detection
and are saved.
As protection against damage to the
drives, the output contacts are interlocked
electromechanically.
Operating voltage
Current consumption KNX
Power consumption KNX
JRA/S type
Number of outputs UP/DOWN
U
rated voltage
N
I
rated current
N
Current detection for travel direction
Maximum switching current
Minimum switching current
Leakage loss per device at max. load
Drives (terminals, output A...X)
Phase L1...L3 (terminal U
)
N
Conductor cross-sectional area, screw terminals
Tightening torque
®
ABB i-bus
KNX
The outputs can be directly controlled on
the device using the manual
pushbuttons. The LEDs on the front of
the device signal the status of the
outputs. The devices require no separate
®
KNX. In
auxiliary voltage.
Individual outputs can be copied or
exchanged to reduce the programming
effort.
The blind/roller shutter actuators are
modular installation devices for
installation in the distribution board on
35 mm mounting rails. The connection to
the ABB i-bus
connection terminals.
21 ... 30 V DC via KNX
< 12 mA
Maximum 250 mW
2.230.5.1
2*
(Interlocked electromechanically)
* independent outputs for up to 2
drives each in parallel operation.
Maximum 230 V AC, 45 ... 65 Hz
6 A
> 300 mA
6 A (AC1/AC3) at 230 V AC or
6 A (AC1/AC3) at 400 V AC
100 mA at 5 V or
10 mA at 10 V or
1 mA at 24 V
< 2 W
For each output, 2 screw terminals (UP/DOWN)
with universal head
2 or 4 screw terminals with universal head
Rigid 0.2...6 mm², flexible 0.2...4 mm²
Flexible with wire end ferrules without/with
plastic sleeve 0.25...4 mm²
Max. 0.6 Nm
Bus connection terminal (black/red), 0.8 mm Ø,
single-core
®
is implemented via bus
4.230.5.1
8.230.5.1
4
8
< 2 W
< 4 W
JRA/S | 2CDC 506 051 D0204 7