ABB i-bus KNX Product Manual page 100

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
No.
4
5
6
7
8
These communication objects can be monitored cyclically. The interval is determined by the monitoring time. If a telegram
with the value 0 is received within the monitoring time, then operation of the blinds/shutters is enabled.
If a telegram with the value 1 is received or no telegram is received during the monitoring period, then the blinds/shutters are
moved to the parameterized Position on wind alarm (or Rain alarm or Frost alarm). Operation via direct telegrams and and
automatic telegrams is disabled.
The first time a telegram with the value 0 is received again after a weather alarm or after the monitoring period has been
exceeded, the blinds/shutters are moved to the parameterizable Position on reset of weather alarm and operation is enabled
again.
The monitoring period is restarted after each telegram is received as well as after programming of the actuator and on bus
voltage recovery. The three wWind alarm communication objects are logically connected via an OR gate, i.e. if a wind alarm
is present for one of the three communication objects or a telegram is not received within the monitoring period, the
blind/shutter moves to the parameterized Position on wind alarm.
Telegram value:
9
98 2CDC 506 051 D0204 | JRA/S
Function
Wind alarm no. 1
Wind alarm no. 2
Wind alarm no. 3
Rain alarm
Frost alarm
0 = No alarm
1 = Alarm (operation disabled)
Not assigned
Object name
Output A...X
Data type
Flags
1 bit
C, R, T, U