Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
Block
Options:
This parameter enables the function Disable. The blind/shutter moves, for example, to a parameterized
position or the operation is blocked. Example: The operation of an internal blind/shutter (internal blind or
roller blind) is inhibited if the window is open.
Activated: The communication object Block is enabled. The following parameter appears.
54 2CDC 506 051 D0204 | JRA/S
Deactivated
Activated
Position during blocking
Options:
No reaction
Up
Down
Stop
Position 1...4
Individual position
This parameter determines the position to be traveled to for the Block function.
No reaction: If the blind/shutter is performing a movement, this movement to the target position
is carried out. If the blind/shutter is at rest, it will remain unchanged in its position.
Up or Down: The blind/shutter moves UP or DOWN.
Stop: If the blind/shutter is performing a movement, this movement stops immediately. The
outputs are disconnected from the voltage supply. If the blind/shutter is at rest, it will remain
unchanged in its position.
Position 1...4: If one of these positions are selected, the blind/shutter moves to a preset
position. The blind/shutter height and slat setting of the corresponding position can be set in
parameter window A: Positions/Presets, p. 72).
Individual position: A freely-definable position is moved to. The following parameters appear.
Position Height in % [0...100]
(0% = top; 100% = bottom)
Position Slat in % [0...100]
(0% = open; 100% = closed)
Note
The parameters for slat adjustment are available exclusively in the operation mode
Control with slat adjustment.
Options:
0...100
These parameters specify the height or the slat position of the blind/shutter.
Deactivated: In the case of a weather alarm, there is no reaction.