Device Technology; Light Controller Lr/S X.16.1; Technical Data - ABB i-bus KNX Product Manual

Light controller with sensor lr/s with lf/u, intelligent installation systems
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
2

Device technology

2.1

Light Controller LR/S x.16.1

LR/S 4.16.1
2.1.1

Technical data

Supply
Outputs control circuit
Sensor input
© 2008 ABB STOTZ-KONTAKT GmbH
Device technology
®
The ABB i-bus
Light Controllers, LR/S x.16.1 (x = 2 or 4) are KNX modular
installation devices (MDRC) in ProM Design for installation in the distribution
board on 35 mm mounting rails. The connection to the ABB i-bus
implemented via a bus connection terminal on the device shoulders.
The LR/S can control dimmable electronic ballasts or transformers with
a 1-10 V interface via two or four outputs – depending on the device
concerned.
For every output a floating switching contact (16 A) for direct switch on and
off of the ballasts are available. The switching relays are particularly suitable
for switching fluorescent lamp loads (AX) to DIN EN 60 669.
Manual switch ON and OFF of the individual outputs is possible in manual
control independently of the bus or auxiliary voltages. The operating element
on the switching relay directly indicates the switch status.
A separate Light Sensor LF/U 2.1 can be separately connected on the Light
Controller for each output. The light sensor measures brightness in closed
rooms. The Light Controller undertakes constant light control for each output
(control circuit) with this brightness value. It is possible to use several Light
Sensors for a single output.
The Light Controller and the connected Light Sensor are supplied with power
via the KNX and do not require any additional power supply.
Operating voltage
Power consumption via KNX
Current consumption KNX
Maximum
LR/S type
Number of control outputs 1-10 V (passive)
Maximum current per control output
Maximum number of ballasts (2 mA/ballast)
Maximum cable length with
maximum load (100 mA)
2)
LF/U 2.1
Number of inputs
Maximum cable length per sensor
21...30 V DC, made available by the bus
Maximum 250 mW
2.16.1
8.5 mA
2.16.1
2
100 mA
1)
50
70 m with cable cross-section 0.8 mm
100 m with cable cross-section 1.5 mm
2 with LR/S 2.16.1 or 4 with LR/S 4.16.1
Per sensor 100 m, Ø 0.8 mm,
P-YCYM or J-Y(ST)Y cable (SELV),
e.g. shielded KNX bus cable
®
is
4.16.1
10 mA
4.16.1
4
100 mA
50
2
2
7