Device Technology; Technical Data - ABB i-bus KNX Product Manual

Valve drive actuator vaa/s x.230.2.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX

Device Technology

2
Device Technology
VAA/S 6.230.2.1
2.1

Technical data

Supply
Outputs
Connections
Operating and display elements
Enclosure
Safety class
Isolation category
The Valve Drive Actuators VAA/S are
modular installation devices in Pro M
Design for installation in the distribution
board on 35 mm mounting rails. The
devices feature six or twelve
semiconductor outputs for control of
Thermoelectric Valve Drives in heating
and cooling systems. The outputs can be
operated at 24...230 V AC.
The outputs are short-circuit and overload
protected.
Bus voltage
Current consumption, bus
Leakage loss, bus
Leakage loss of the device at max. load
6 or 12 semiconductor outputs
Rated voltage U
n
Rated current I
per output
n
Inrush current per output
Caution:
When valve drives (e.g. TSA/K) are connected in
parallel, the technical data of the respective
valve drive must be observed! The inrush current
(750 mA) or rated current (160 mA) of the output
may not be exceeded.
KNX
Output terminals
Button/LED
Button
and LED
One button
and LED
per output
One button
and LED
for every 3 outputs
IP 20
II
overvoltage category
pollution degree
The outputs can be directly controlled
using the manual buttons. The LEDs on
the front of the device signal the status
of the outputs.
The connection to the ABB i-bus
is implemented via a bus connection
terminal.
The devices do not require an additional
auxiliary power supply.
21...32 V DC
< 12 mA
maximum 250 mW
maximum 2 W at VAA/S 6.230.2.1
maximum 4 W at VAA/S 12.230.2.1
for every 3 non-isolated outputs in the group.
Short circuit and overload protected
24...230 V AC, 50/60 Hz
160 mA resistive load at T
up to 45 °C
amb
maximum 750 mA for 10 s at T
A
via bus connection terminals
via universal head screw terminals
2
0.2... 4 mm
stranded, 2 x 0.2...2.5 mm
2
0.2...6 mm
single core, 2 x 0.2...4 mm
for assignment of the physical address
for toggling between manual
operation/operation via ABB i-bus
for control (ON/OFF) of the output and
display of the status
for reset and indication of a fault
e.g. short circuit and overload
to EN 60 529
to EN 61 140
III to DIN EN 60 664-1
2 to EN 60 664-1
VAA/S x.230.2.1 | 2CDC 508 101 D0201 7
®
KNX
up to 60 °C
2
,
2
®
and displays