Section 7
Station communication
MicroSCADA
GOOSE
Control
IEC05000734 V1 EN-US
Figure 12:
7.1.2

Setting guidelines

There are two settings related to the IEC 61850–8–1 protocol:
Operation : User can set IEC 61850 communication to On or Off .
GOOSEPortEd1 : Selection of the Ethernet link where GOOSE traffic shall be sent and received.
This is only valid for Edition 1 and can be ignored if Edition 2 is used. For Edition 2, the
Ethernet link selection is done with the Ethernet Configuration Tool (ECT) in PCM600.
7.1.3

Horizontal communication via GOOSE

7.1.3.1

Sending data

In addition to the data object and data attributes of the logical nodes, it is possible to send
the outputs of the function blocks using the generic communication blocks. The outputs of
this function can be set in a dataset and be sent in a GOOSE Control Block to other subscriber
IEDs. There are different function blocks for different type of sending data.
Generic communication function for Single Point indication SPGAPC, SP16GAPC
Application
Generic communication function for Single Point Value (SPGAPC) function is used to send one
single logical output to other systems or equipment in the substation. SP16GAPC can be used
to send up to 16 single point values from the application functions running in the same cycle
time. SPGAPC has one visible input and SPGAPC16 has 16 visible inputs that should be
connected in the ACT tool.
Setting guidelines
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
60
Station HSI
IED
IED
A
A
Protection
Example of a broadcasted GOOSE message
© Copyright 2017 ABB. All rights reserved
IED
IED
A
A
Control and protection
Control
1MRK 511 445-UEN B
Gateway
IED
A
Protection
en05000734.vsd
GUID-9888ECAD-8221-4B31-A443-EB1E3A9022C4 v1
Switchgear control unit SAM600-IO
Application manual
SEMOD55317-5 v7
SEMOD55999-1 v4
SEMOD55350-5 v8
SEMOD55376-5 v5
SEMOD55402-1 v3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion sam600-io

Table of Contents