Specifications For The Cisco Mds 9506 Power Supplies; Power Specifications For The Cisco Mds 9506 Director - Cisco AJ732A - MDS 9134 Fabric Switch Installation Manual

Cisco mds 9500 series hardware installation guide (ol-17467-02, october 2008)
Hide thumbs Also See for AJ732A - Cisco MDS 9134 Fabric Switch:
Table of Contents

Advertisement

Appendix D
Technical Specifications
S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m .

Specifications for the Cisco MDS 9506 Power Supplies

The following applies to AC power supplies on the Cisco MDS 9506 only:
Caution
The DS-C9506 equipment is suitable for use on TN power systems and the IT-power system connection
of Norway (max 230 v phase-phase). If connected to a 230/400-V IT power system, beware of
high-leakage current. Earth connection is essential before connecting the supply.
The 1900-W AC power supply provides power based upon the input voltage:
A 110-VAC power cord (CAB-7513AC=) must be ordered separately.
Table D-15
Table D-15
Description
1900-W AC Power Supply
Type
Voltage
Current rating
Frequency
Output capacity
Output voltage at 110/120 3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 20.4 A.
Output voltage at 200/240 3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 37.4 A.
1900-W DC Power Supply
Voltage
Current rating
Terminal block
Output capacity
Output voltage
OL-17467-02
Maximum of 1050 W at input of 100 to 120 VAC
Maximum of 1900 W at input of 200 to 240 VAC
lists the specifications for the Cisco MDS 9506 power supplies.
Specifications for Cisco MDS 9506 Power Supplies
Specification
Autoranging input with power factor corrector.
100 to 240 VAC (±10%).
12 A maximum at 100 to 120 VAC and 1050-W
output.
12 A maximum at 200 to 240 VAC and 1900-W
output.
Note
50/60 Hz (nominal) (±3 Hz for full range).
1050 W maximum (at input of 100 to 120 VAC).
1900 W maximum (at input of 200 to 240 VAC).
-48 to -60 VDC continuous.
50 A at -48 VDC, 40 A at -60 VDC, 60 A at -40.5
VDC.
Accommodates 2 to 14 AWG copper conductors.
Use 90°C copper conductors for North American
installations.
Note
1900 W maximum (at input of -48 to -60 VDC).
3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 37.4 A.

Power Specifications for the Cisco MDS 9506 Director

For current ratings of plugs, see
on page
E-9.
Actual size of the wire required is
determined by the installer or local
electrician. Terminal block material is rated
at 302°F (150°C).
Cisco MDS 9500 Series Hardware Installation Guide