70 Program features
WARNING! Store the pass code in a safe place – even ABB cannot open
the user lock if the pass code is lost.
• In
96.102 User lock
(ABB recommends to select all the actions unless otherwise required by the
application).
• Enter an invalid pass code into
• Activate
96.08 Control board
• Make sure that the parameters
enter another random pass code into
To reopen the lock, enter your pass code into
make parameters
Settings
Parameters
96.02
Sine filter support
With a sine filter connected to the output of the drive, the drive must use scalar
motor control mode, and limit the switching and output frequencies to
• prevent the drive from operating at filter resonance frequencies, and
• protect the filter from overheating.
When using ABB sine filters (available separately), this is done automatically
when you switch bit 1 of
Contact your local ABB representative before connecting a sine filter from
another manufacturer.
Settings
Parameter
95.15 Special HW settings
Dead-band function
With the Dead-band function, you can freeze the AI reference for a defined area
(that is, dead-band) or ignore a low AI reference caused by possible
electromagnetic interference issues.
In voltage mode:
AI dead band value = 10V* AI dead band (12.110) * 0.01
In current mode:
AI dead band value = 20mA* AI dead band (12.110) * 0.01
functionality, define the actions that you want to prevent
96.02 Pass
boot, or cycle the power to the drive.
96.100...96.102
visible.
96.102...96.102
(page 249) and
96.100...96.102
95.15 Special HW settings
code.
are hidden. If they are not,
96.02 Pass
code.
96.02 Pass
(page 257).
on.
(page 247).
code. This will again