96 System - ABB ACQ80 Firmware Manual

Standard program control
Table of Contents

Advertisement

248 Parameters
No.
Name/Value
95.26
Motor disconnect
switch
Disable
Enable
95.200 Cooling fan
mode
Auto
Always on
96

96 System

96.01
Language
Not selected
English
Italiano
Description
Enables the use of the motor disconnect switch.
When enabled, the drive does not trip to a fault
when it detects the disconnection but remains
operational and returns to normal operation
after a reconnection.
When this parameter is enabled, the drive will go
through the following sequence:
1. Motor is disconnected: Drive detects the
disconnection and indicates it with warning
A784. The drive remains in operation and waits
for motor reconnection.
2. Motor is reconnected: Drive detects the
reconnection, removes the warning and returns
to normal operation. The last active reference
before the disconnection is in use.
Note: This feature is only available in scalar
mode. This parameter does not affect vector
mode behavior.
Motor disconnect switch disabled.
Motor disconnect switch enabled.
Selects the fan control type. The fan control
functionality enables heat dissipation from the
drive and avoids dust accumulation in the drive.
Controls the fan automatically according to the
temperature changes of the drive.
Fan runs continuously with the maximum speed
(50Hz).
Language selection; access levels; macro
selection; parameter save and restore; control
unit reboot; user parameter sets; unit selection.
Selects the language of the parameter interface
and other displayed information when viewed on
the control panel.
Notes:
• Not all languages listed below are necessarily
supported.
• This parameter does not affect the languages
visible in the Drive composer PC tool. (Those
are specified under View – Settings – Drive
default language.)
None.
English.
Italian.
Def/
FbEq16
Disable
0
1
Auto
0
1
Not
selected
0
1033
1040

Advertisement

Table of Contents
loading

Table of Contents