83 Pump Cleaning - ABB ACQ80 Firmware Manual

Standard program control
Table of Contents

Advertisement

242 Parameters
No.
Name/Value
82.45
Pressure check
delay
0.00...3600.00 s
82.46
Dry run current
limit
0.00...3000.00 A
82.47
Dry run trip
monitor time
1.0...300.0 s
82.48
Dry run reset
time
1.0...18000.0 s
83

83 Pump cleaning

83.01
Pump cleaning
status
Disabled
Clean pump
No triggers
configured
Waiting for
triggering
83.02
Pump cleaning
progress
0.0...100.0%
Description
Defines the delay time at which the pressure
supervisions are inactive.
You can adjust check delay for a system in which
the pressure does not increase immediately after
starting the motor.
Pressure check delay time.
Defines the dry run current limit. When the actual
current goes below the dry run current limit for a
defined time (82.47), the drive considers it as a
dry run condition and trips on the fault,
Running
dry.
Note: This parameter is not applicable, if the
parameter
82.02 Dry run source
DI.
Current limit.
Defines the time to monitor dry run current limit.
After the defined time elapses, the drive
considers it as dry run condition and trips on the
fault,
D4B0 Running
Note: This parameter is not applicable, if the
parameter
82.02 Dry run source
Run trip monitor time.
Defines the rest time to reset the dry run fault
(D4B0). The drive starts automatically if it
receives a start command.
Dry run reset time.
Settings for the pump cleaning sequence.
See section
Pump cleaning
Displays the status of pump cleaning.
Pump cleaning is disabled.
Pump cleaning is active.
Pump cleaning is not active.
Waiting for triggering signal.
Displays the pump cleaning progress.
Percentage
selection is set to
dry.
is DI.
(page 47).
Def/
FbEq16
3.00 s
1 = 1 s
0.00 A
D4B0
100 = 1
120.0
10 = 1
120.0
10 = 1
Disabled
0
1
2
3
0
10 = 1