232 Parameters
No.
Name/Value
80.03
Total flow
0.00...
21474836.00 m
80.04
Specific energy
0.00...32767.95
3
m
/kWh
80.05
Estimated pump
head
0.00...
32767.00 m
80.06
Today's flow
0.00...
21474836.00 m
80.07
Sensored flow
0...2147483648
80.11
Flow feedback 1
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
AI1 percent
AI2 percent
Feedback data
storage
Other
80.12
Flow feedback 2
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
Description
Shows cumulative calculated flow.
Total flow.
3
Shows the ratio of pump flow rate and power
input.
Specific energy of the pump.
Shows the estimated head produced by the
pump.
Estimated pump head.
Shows the measured flow of current day in cubic
meter.
Note: You can reset this value using the
parameter
80.29 Total flow
Measured flow of the current day.
3
Shows the flow rate based on the counts
received from the sensors. This value is displayed
when the parameter
selected as
DI
based.
Measured flow rate.
Selects the source for the flow feedback 1.
Feedback not used.
12.12 AI1 scaled value
12.22 AI2 scaled value
11.39 Freq in 1 scaled value
12.101 AI1 percent value
12.102 AI2 percent value
40.91 Feedback data storage
Source selection (see
page 80).
Selects the source for the flow feedback 2.
Feedback not used.
12.12 AI1 scaled value
12.22 AI2 scaled value
11.39 Freq in 1 scaled value
reset.
is
80.13 Flow function
(see page 110).
(see page 112).
(see page 107).
(see page 114).
(see page 114).
(see page 204).
Terms and abbreviations
(see page 110).
(see page 112).
(see page 107).
Def/
FbEq16
0.00
1 = 1
0.00
1 = 1
3
m
/kWh
-
1 = 1 m
0.00
10 = 1
0
1 = 1
Not
selected
0
1
2
3
8
9
10
on
-
Not
selected
0
1
2
3