ABB ACQ80 Firmware Manual page 113

Standard program control
Table of Contents

Advertisement

No.
Name/Value
12.25
AI2 unit selection
V
mA
12.26
AI2 filter time
0.000...
30.000 s
12.27
AI2 min
0.000...22.000
12.28
AI2 max
0.000...
22.000 mA
Description
Selects the unit for readings and settings related
to analog input AI2.
Note: In firmware ASCL2 and ASCL4), this setting
must match the corresponding hardware setting
on the drive control unit. chapter
installation
, section Switches in the
manual
of the drive and the default control
connections for the macro in use in chapter
(page 75). Control board reboot
Control macros
(either by cycling the power or through
parameter
96.08 Control board
validate any changes in the hardware settings.
Volts.
Milliamperes.
Defines the filter time constant for analog input
AI2. See parameter
12.16 AI1 filter
Filter time constant.
Defines the minimum site value for analog input
AI2.
Set the value actually sent to the drive when the
analog signal from plant is wound to its
minimum setting.
Minimum value of AI2.
Defines the maximum site value for analog input
AI2.
Set the value actually sent to the drive when the
analog signal from plant is wound to its
maximum setting.
Maximum value of AI2.
Parameters 113
Electrical
Hardware
boot) is required to
time.
Def/
FbEq16
mA
2
10
0.100 s
1000 = 1 s
4.000 mA
1000 =
1 unit
20.000 mA
1000 =
1 unit