182 Parameters
No.
Name/Value
35.23
Temperature 2
warning limit
-60...5000 °C or
-76...9032 °F
35.24
Temperature 2 AI
source
Not selected
AI1 actual value
AI2 actual value
Other
35.50
Motor ambient
temperature
-60...100 °C or
-76 ... 212 °F
Description
Defines the warning limit for temperature
supervision function 2. When measured
temperature 1 exceeds the limit, warning
External temperature 2
The unit is selected by parameter
selection.
Warning limit for temperature monitoring
function 2.
Specifies the analog input when the setting of
35.11 Temperature 1 source
measurement through an analog input.
None.
Analog input AI1 on the control unit.
Analog input AI2 on the control unit.
Source selection (see
page 80).
Defines the ambient temperature of the motor
for the motor thermal protection model.
The unit is selected by
selection. The motor thermal protection model
estimates the motor temperature on the basis of
parameters 35.50...35.55. The motor
temperature increases if it operates in the region
above the load curve, and decreases if it operates
in the region below the load curve.
WARNING! The model cannot protect the
motor if the motor does not cool properly
because of dust, dirt, etc.
Ambient temperature.
is generated.
96.16 Unit
requires
Terms and abbreviations
parameter96.16 Unit
Def/
FbEq16
110 °C or
230 °F
A492
1 = 1 unit
Not
selected
0
1
2
on
-
20 °C or
68 °F
1 = 1°