Standard Di, Ro - ABB ACQ80 Firmware Manual

Standard program control
Table of Contents

Advertisement

100 Parameters
No.
Name/Value
07.30
Adaptive
program status
Bit
Name
0
Initialized
1
Editing
2
Edit done
3
Running
4...13 Reserved
14
State changing
15
Faulted
0000h...FFFFh
07.31
AP sequence
state
0...20
10

10 Standard DI, RO

10.02
DI delayed status
Bit
0
1
2
3
4
5
6...15 Reserved
0b0000...0b1111 Delayed status for digital inputs.
Description
Shows the status of the adaptive program.
See section
Description
1 = Adaptive program initialized
1 = Adaptive program is being edited
1 = Editing of adaptive program finished
1 = Adaptive program running
1 = State change in progress in adaptive
programming engine
1 = Error in adaptive program
Adaptive program status.
Shows the number of the active state of the
sequence program part of the adaptive program
(AP). If adaptive programming is not running, or
it does not contain a sequence program, the
parameter is zero.
Configuration of digital inputs and relay outputs.
Shows the status of digital inputs DI1...DI6. Bits
0...5 reflect the delayed status of DI1...DI6.
Example: 0000000000010011b = DI5, DI2 and DI1
are on, DI3, DI4 and DI6 are off.
This word is updated only after a 2 ms
activation/deactivation delay. When the value of
a digital input changes, it must remain the same
in two consecutive samples, that is for 2 ms, for
the new value to be accepted.
This parameter is read-only.
Name
Description
DI1
1 = Digital input 1 is ON.
DI2
1 = Digital input 2 is ON.
DI3
1 = Digital input 3 is ON.
DI4
1 = Digital input 4 is ON.
DI5
1 = Digital input 5 is ON.
DI6
1 = Digital input 6 is ON.
Def/
FbEq16
-
1 = 1
1 = 1
0b0000
1 = 1