References; References For The Abb Drives Profile And Dcu Profile; Actual Values; Actual Values For The Abb Drives Profile And Dcu Profile - ABB ACQ80 Firmware Manual

Standard program control
Table of Contents

Advertisement

360 Fieldbus control through the embedded fieldbus interface (EFB)

References

References for the ABB Drives profile and DCU Profile

The references are provided by MPPT and does not depend on any user settings.

Actual values

Actual values for the ABB Drives profile and DCU Profile

The ABB Drives profile supports the use of two fieldbus actual values, ACT1 and
ACT2. The actual values are 16-bit words each containing a sign bit and a 15-bit
integer. A negative value is formed by calculating the two's complement from
the corresponding positive value.
The actual values are scaled as defined by parameters
46.04; which scaling is in use depends on the setting of parameters
and
act1 type
58.29 EFB act2 type
Fieldbus
(see page 222).
99.09
(with motor nominal speed)
20000
99.08
(with motor nominal frequency)
46.03
(with torque reference)
10000
46.04
(with power reference)
0
0
-(46.03) (with torque reference)
-10000
-(46.04) (with power reference)
-(99.09) (with motor nominal speed)
-20000
-(99.08) (with motor nominal frequency)
99.08
,
99.09,
Drive
and
46.03
58.28 EFB