ABB ACQ80 Firmware Manual page 230

Standard program control
Table of Contents

Advertisement

230 Parameters
No.
Name/Value
79.39
Pump start
interlock
Disable
Enable
DI1
DI2
DI3
DI4
DI5
DI6
Other [bit]
79.41
Start DC voltage
225...800 V
79.42
PV cell min
voltage
225...800 V
79.43
PV cell max
voltage
225...800 V
Description
Selects the interlock source for pump start and
stop. When the interlock is disabled, pump
cannot be started in any operating modes and
tank level sensor operation cannot function.
0 = Pump start interlock is disabled.
1 = Pump start interlock is enabled.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Source selection (see
page 80).
Defines the minimum DC voltage for drive to
start running the pump motor. The pump motor
stops running if the voltage goes below this
value.
Note: If you change this value while the inverter is
running, the changed value is effective only
during the
next start
DC voltage.
Defines the minimum DC voltage below which
the
drive turns off all the controls.
Note: The drive stops operating below this
voltage.
DC voltage.
Defines the maximum DC voltage. At any value
above this voltage, the drive trips due to
fault.
max volt
DC voltage.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
Terms and abbreviations
D4B1 PV
Def/
FbEq16
Enable
0
1
2
3
4
5
6
7
on
-
225
1 = 1
225
1 = 1
800
1 = 1