ABB ACQ80 Firmware Manual page 247

Standard program control
Table of Contents

Advertisement

No.
Name/Value
External 24V
95.15
Special HW
settings
Bit
Name
0
Reserved
1
ABB Sine filter
2...15 Reserved
0b0000...0b111
1
95.20
HW options word
1
Bit
Name
0
Supply
frequency 60
Hz
1...12
Reserved
13
du/dt filter
activation
14...15 Reserved
0b0000...
0b1111
Description
The drive control board is powered from an
external power
supply.
Contains hardware-related settings that can be
enabled and disabled by toggling the specific
bits.
Note: The installation of the hardware specified
by this parameter may require derating of drive
output, or impose other limitations. Refer to the
hardware manual of the drive.
Information
1 = An ABB sine filter is connected to the output of the
drive.
Hardware options configuration word.
Specifies hardware-related options that require
differentiated parameter defaults.
This parameter is not affected by a parameter
restore.
Value
If you change the value of this bit, you have to do a
complete reset to the drive after the change. After
reset you have to reselect the macro to be used.
See section
Differences in the default values between
50 Hz and 60 Hz supply frequency settings
0 = 50 Hz.
1 = 60 Hz.
When active, an external du/dt filter is connected to
the drive/inverter output. The setting will limit the
output switching frequency, and force the fan of the
drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
Hardware options configuration word.
Parameters 247
Def/
FbEq16
1
0b0000
1 = 1
0b0000
on page 272.
1 = 1

Advertisement

Table of Contents
loading

Table of Contents