252 Parameters
No.
Name/Value
96.07
Parameter save
manually
Done
Save
96.08
Control board
boot
No action
Reboot
96.10
User set status
n/a
Loading
Saving
Faulted
User1 IO active
User2 IO active
Description
Saves the valid parameter values to the
permanent memory on the drive control unit to
ensure that operation can continue after cycling
the power.
The new parameter values are saved
automatically when changed from a PC tool or
control panel, after the drive is powered on for
more than 60 seconds.
Save the parameters with this parameter
• to store values sent from the fieldbus
• when using external +24 V DC power supply to
the control unit: to save parameter changes
before you power down the control unit. The
supply has a very short hold-up time when
powered off.
• to save the parameter value changes when the
drive is powered off within 60 seconds after
being powered on.
Save completed.
Save in progress.
Changing the value of this parameter to 1
reboots the control unit (without requiring a
power off/on cycle of the complete drive
module).
The value reverts to 0 automatically.
1 = No action.
1 = Reboot the control unit.
Shows the status of the user parameter sets.
This parameter is read-only.
See also section
User parameter sets
No user parameter sets have been saved.
A user set is being loaded.
A user set is being saved.
Invalid or empty parameter set.
User set 1 has been selected by parameters
User set I/O mode in1
in2.
User set 2 has been selected by parameters
User set I/O mode in1
in2.
(page 69).
and
96.13 User set I/O mode
and
96.13 User set I/O mode
Def/
FbEq16
Done
0
1
No action
0
1
n/a
0
1
2
3
4
96.12
5
96.12