Programming Function Blocks and Features
Advanced Splitter Output (ADV SPLITTER)
This function can be used for heat/cool applications. It splits an input into 3 independently scaled outputs:
CVn_A1, CVn_A2 and CVn_A3 ( Figure 4-14 ). For each output, when the input is between IN LO LIM
and IN HI LIM, the output is scaled between the OUT LO LIM and OUT HI LIM. Each output holds its
OUT LO LIM value when the input < the IN LO LIM value for that output. Each output holds its OUT HI
LIM value when the input > the IN HI LIM value for that output. Output limits (OUT LO LIM & OUT HI
LIM) cannot exceed 100% but can be negatively sloped (OUT HI LIM < OUT LO LIM).
Table 4-41 describes the Advanced Splitter prompts. See Table 4-2 for additional prompts.
134
100
A1
OUTPUT
VALUE
(%)
0
0
30
INPUT SOURCE VALUE (%)

Figure 4-14 Advanced Splitter (Default Outputs)

FEEDBACK
OV
SPLIT
LOOP

Figure 4-15 Heat/Cool Configuration

VPR & VRX – User Manual
A2
A3
60
90
BC
FEEDBACK #1
A1
SPLITTER
CV
INPUT
A2
FEEDBACK#2
100
BC
AO
AO
AO
BC