Table 4-25 Logic Prompts; Figure 4-6 Logic Signal Flow - Honeywell VPR100 User Manual

Table of Contents

Advertisement

Logic
The input or inputs are processed by a logic operator. Call the result of this logic operation "Result".
Result is a pulse that goes ON(1) when the logic is true, and OFF(0) when the logic is not true. Result is
then processed according to the specified condition type and condition time. The final output is a discrete
pulse CVn OS. See Figure 4-6 .
Table 4-25 describes the Logic prompts. See Table 4-2 for additional prompts.
Prompt
OPERATOR
AND, OR, XOR, RESET/SET FF,
TOGGLE/FF, ONE SHOT, PASS
INPUT A
OFF, discrete parameter, 0, 1.
INPUT B
INPUT C
INPUT D
INPUT E
INPUT F
INPUT G
INPUT H
CONDITION TYPE
NONE, DELAY, EXTEND, PULSE,
RT PULSE
CONDITION TIME
OFF or number
12/00
Inputs
A
B
C
LOGIC
D
E
OPERATOR
F
G
H

Figure 4-6 Logic Signal Flow

Table 4-25 Logic Prompts

Range/Selections
VPR & VRX – User Manual
Programming Function Blocks and Features
CONDITION
TYPE
Result
CVn OS
&
CONDITION
TIME
Definition
See Table 4-26.
Program at least 2 inputs. Only inputs programmed
with parameter, 1, or 0 are processed with the
operator.
See Table 4-20 on page 111.
Enter number of seconds of condition time. See
Table 4-20 on page 111.
117