How to start a profiler
A profiler can be started from the Ready, Hold or End state.
Step
1
Press Display button until the Setpoint Trend is
displayed.
Or
Press the Display button until a Setpoint Bar
Graph display is shown. Press the Tab button
to move the cursor to the TREND text under
the desired profile at the bottom of the display.
Press Enter to display the Setpoint Profile
Trend display for that profile.
2
Press Tab button to display the profile menu.
3
Cursor is on Start. Press Enter.
ATTENTION
A profile can also be started by pressing the START or F1 button, but only if that profile's START parameter
was configured as SY1 F1. See Section 5.3.
12/00

Table 5-13 Profiler Starting Procedure

Action
VPR & VRX – User Manual
Result/Notes
SP1
PROFIL01
PV
0.00
SP
0.00
SEG1/9
SP1
PROFIL01
START
HOLD
RESET
ADVANCE
SHUTDOWN
EVENTS
DETAIL
SUMMARY
EDIT
LOAD
PV
0.00
SP
0.00
SEG1/9
Profiler starts running at segment #1 if in Ready
or End or resumes running from its Hold state. If
in Ready state and Hot Start has been activated,
profiler will start at the first point in the profile
where the present value of PV #1 occurs. Event
outputs assume their states as of the beginning of
the running segment. Profiler status on lower
right of display indicates RUN after you start the
profiler
Setpoint Profiler
500.00
0.00
0:00:00
READY
500.00
0.00
0:00:00
READY