Editing Segments
Use the following prompts to map out each segment's value, time, and events. Up to 63 segments are
programmable per profile.
Prompt
NEXT SEGMENT
PREVIOUS SEGMENT
VALUE
AUX VALUE
TIME
GUAR SOAK #1
GUAR SOAK #2
EDIT EVENTS
12/00

Table 5-6 Edit Segments Prompts

Range/Selections
OFF or number
OFF or number
OFF or Positive number
ON or OFF
ON or OFF
EVENT #1
.
.
.
EVENT #16
VPR & VRX – User Manual
Definition
Select this to edit the next segment.
Select this to edit the previous segment
This prompt is active for soak segments
and value/duration ramp types. Enter the
value of the segment.
This value is an auxiliary soak output of
the profile. The output is identified as
SPn A1 and remains constant for the
duration of the segment.
The purpose of the number entered here
depends on the ramp type of the profile.
See 4 types of ramp segments on page
186 for details.
ON means the profiler will Hold during this
segment if deviation between PV #1 and
the profiler output exceeds the
guaranteed soak limits in Table 5-5. OFF
means the profiler will not Hold during this
segment due to deviation. See
Guaranteed Soak on page 191 for details.
ON means the profiler will Hold during this
segment if deviation between PV #2 and
the profiler output exceeds the
guaranteed soak limits in Table 5-5. OFF
means the profiler will not Hold during this
segment due to deviation. See
Guaranteed Soak on page 191 for details.
Enter the state of up to 16 discrete
outputs of this segment. These outputs
can be used to trigger any action requiring
a discrete signal, such as a relay or
another function block.
An event stays on or off for the entire
segment.
To trigger events in the middle of a
segment, you must divide the segment
into 3 segments. See Segment Events on
page 192 for details.
Setpoint Profiler