Set Analog Outputs
This menu item will appear if the optional analog outputs are installed. It lets you adjust various analog
output parameters.
Four output types are available: current output (CAT), voltage output (VAT), time proportion/duration
adjusting (DAT) and Position Proportion (PP). Outputs 1 through 3 may be dedicated to CAT or VAT
types. Outputs 4 and 5 may only be DAT types.
Prompt
FAILSAFE VALUE
IMPULSE TIME
SENSITIVITY
POS ALGORITHM
Reset Totalizers
Select this item to display a list of all resettable Totalizers and their current values. If the Totalizer is non-
resettable it will not appear. You may use this display to reset one Totalizer, or all at once. Note that some
or all Totalizers may be configured to be non-resettable. Use the Up Arrow, Down Arrow and Enter
buttons to select an item from the list. At the prompt "RESET", press Enter to reset the Totalizer.
To reset all Totalizers, select the menu line "RESET ALL TOTALIZERS" and press Enter at the prompt.
All resettable Totalizers will be reset. Only resettable totalizers are shown here.
12/00
Enter a value of 0 to 100% or an analog parameter for the initial output.
This is the initial output on "cold start". If the failsafe value is set to off, the
output will go to 0.
For DAT outputs, use the Up Arrow, Down Arrow and Enter buttons to
adjust the impulse time. Impulse time must be ≥ 1 second. Impulse time is
the cycle time for on and off cycling of the output. For example, an impulse
time of 150 seconds will cause the output to be on for 75 seconds and off
for 75 seconds when the input source is at 50.
Applies to PP type AO only. This is a percentage value. This value should
be set to the highest number which does not cause drive motor oscillation.
Applies to PP type AO only. The PP and Auto algorithms require a feedback
analog input. The selection of Auto allows normal PP feedback positioning
of a drive motor when the feedback input is good, and defaults to DIAT
operation if the slidewire feedback input fails. Use of Auto requires that the
loop type be DIAT. The PP algorithm can be used with all other PID loop
types.
VPR &VRX – User Manual
Online Operation Using Menus
Definition
245