CEMS Rolling Average (CEM Rolling Avg)
Outputs a rolling mean average CVn OV over the specified Average Period. Average is updated every
Frame Period thereafter. Samples are taken at every scan cycle of the instrument, except when Calibrate
Hold is ON(1).
Input
Table 4-49 describes the CEMS Rolling Average prompts. See Table 4-2 for additional prompts.
Prompt
RANGE LOW
RANGE HIGH
INPUT
RESET
TIME UNITS
AVERAGE PERIOD
FRAME PERIOD
CALIBRATE HOLD
12/00
Time between samples = 1 machine scan cycle
Frame Period
Average Period
First average

Figure 4-17 CEMS Rolling Average

Table 4-49 CEMS Rolling Average Prompts

Range/Selections
OFF or number
OFF, analog parameter,
number
OFF, discrete parameter, 0,
1
Seconds, minutes, hours, or
days.
OFF or number
OFF or number
OFF, discrete parameter, 0,
1
VPR & VRX – User Manual
Programming Function Blocks and Features
Second average
Third average
Enter the output's display limits. Output is not clamped
or flashed when it exceeds these limits.
Input to be averaged
When discrete is ON(1), average is reset to zero; when
ON(1)-to-OFF(0), average restarts.
Time units of the averaging period
Number of time units per average period.
Number of time units per Frame Period. Must divide
evenly into Average Period.
When ON(1), no samples are taken and the output is
held.
Definition
143