Figure 4-12 Advanced Splitter (Default Outputs); Figure 4-13 Heat/Cool Configuration - Honeywell VRX180 User Manual

Honeywell video recorder user manual
Table of Contents

Advertisement

Advanced Splitter Output (ADV SPLITTER)
This function can be used for heat/cool applications. It splits an input into 3 independently scaled
outputs: CVn_A1, CVn_A2 and CVn_A3 (Figure 4-12). For each output, when the input is between IN
LO LIM and IN HI LIM, the output is scaled between the OUT LO LIM and OUT HI LIM. Each output
holds its OUT LO LIM value when the input < the IN LO LIM value for that output. Each output holds its
OUT HI LIM value when the input > the IN HI LIM value for that output. Output limits (OUT LO LIM &
OUT HI LIM) cannot exceed 100% but can be negatively sloped (OUT HI LIM < OUT LO LIM).
Table 4-41 describes the Advanced Splitter prompts. See Table 4-2 for additional prompts.
100
A1
OUTPUT
VALUE
(%)
0
0
30

Figure 4-12 Advanced Splitter (Default Outputs)

FEEDBACK
OV
SPLIT
LOOP

Figure 4-13 Heat/Cool Configuration

Video Recorder – User Manual
Programming Function Blocks and Features
A2
A3
60
90
INPUT SOURCE VALUE (%)
BC
FEEDBACK #1
A1
SPLITTER
INPUT
CV
A2
FEEDBACK#2
100
BC
AO
AO
AO
BC
133