Turning Up a Node
DLP-G428 Installing Fiber-Optic Cables from the 40-WSS-C/40-WSS-CE and 40-DMX-C/40-DMX-CE Cards to the 40-Channel Patch Panel Tray
Step 2
On the patch panel, locate the MPO cables and connectors.
Step 3
At the 40-WSS-C/40-WSS-CE card in the node, plug the MPO connector labeled 1 RX on an MPO cable
(Figure 4: MPO Cable, on page
Step 4
Plug the MPO connector labeled 2-RX into the Add RX (36.6–42.1) port on the card.
Step 5
Plug the MPO connector labeled 3-RX into the Add RX (42.9–48.5) port on the card.
Step 6
Plug the MPO connector labeled 4-RX into the Add RX (49.3–54.9) port on the card.
Step 7
Plug the MPO connector labeled 5-RX into the Add RX (55.7–61.4) port on the card.
Caution
Step 8
At the adjacent 40-DMX-C/40-DMX-CE card in the same side of the shelf, plug the MPO connector labeled
1 TX on the MPO cable into the top Drop TX (30.3–35.8) port of the card.
Step 9
Plug the MPO connector labeled 2-TX into the Drop TX (36.6–42.1) port on the card.
Step 10
Plug the MPO connector labeled 3-TX into the Drop TX (42.9–48.5) port on the card.
Step 11
Plug the MPO connector labeled 4-TX into the Drop TX (49.3–54.9) port on the card.
Step 12
Plug the MPO connector labeled 5-TX into the Drop TX (55.7–61.4) port on the card.
Caution
Step 13
Repeat Steps
Step 14
Return to your originating procedure (NTP).
36) into the top Add RX (30.3–35.8) port of the card.
When you close the patch panel tray, the cables must not be pinched, and the cable bend radius
must be equal to or greater than the minimum radius that is recommended in your site specifications.
As you route each cable through the patch panel tray, make sure that adequate cable slack remains.
The following figure shows the 40-channel patch panel ports and corresponding wavelengths.
Figure 12: 40-Channel (15454-PP-80) Patch Panel Port Wavelengths
When you close the patch panel tray, the cables must not be pinched, and the cable bend radius
must be equal to or greater than the minimum radius that is recommended in your site specifications.
As you route each cable through the patch panel tray, make sure that adequate cable slack remains.
2
through
12
to cable the other side of the shelf to the second patch panel.