Chapter 2
Installing a Cisco Nexus 7009 Chassis
S e n d d o c u m e n t c o m m e n t s t o n e x u s 7 k - d o c f e e d b a c k @ c i s c o . c o m
Use four M4x8 pan-head screws to loosely fasten the top hood to each of the two cable management
Step 5
frames as shown in
Tighten each of the four screws that fasten the top hood to the cable management frames to 11 to 15 in-lb
Step 6
(1.2 to 1.7 N·m).
Tighten each of the eight screws that fasten the cable management frames to the rack-mount brackets to
Step 7
11 to 15 in-lb (1.2 to 1.7 N·m).

Installing the Front Door and Air Intake Frame

If you need to install the optional double-hinged door and air intake frame, you must install them after
installing the cable management frame on the chassis.
To install the front door and air intake frame to the Cisco Nexus 7009 cable management system, follow
these steps:
Position the left door stop on the middle of the left cable management frame and fasten it with two
Step 1
M3x10 pan-head screws as shown in
N·m).
Figure 2-17
OL-23069-06
Figure
2-16.
Figure
Attaching the Left Door Stop
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
Installing the Front Door and Air Intake Frame
2-17. Tighten these two screws to 5 to 7 in-lb (0.6 to 0.8
2-27