Cisco Nexus 7000 Series Hardware Installation And Reference Manual page 82

Hide thumbs Also See for Nexus 7000 Series:
Table of Contents

Advertisement

Installing the Bottom-Support Rails on the Rack
S e n d d o c u m e n t c o m m e n t s t o n e x u s 7 k - d o c f e e d b a c k @ c i s c o . c o m
Figure 3-1
1
For the first and heaviest Cisco Nexus 7010
chassis installed in a rack, position two
bottom-support rails at the lowest RU on the
rack.
2
For the second Cisco Nexus 7010 chassis
installed in a rack, position two
bottom-support rails immediately above the
first installed switch.
Use a Phillips screwdriver to screw in three M6 x 19 mm or 12-24 x 3/4 in. Phillips screws on each end
Step 2
of each rail (using a total of 12 screws for both brackets) as shown in
Three of the screw holes on each end of the bottom-support rail align to the screw holes in the mounting
Note
rail. Use a screw in each of these screw holes.
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
3-6
Positioning the Bottom-Support Rails
Chapter 3
Installing a Cisco Nexus 7010 Chassis
3
Allow at least 36.75 inches (93.4 cm) (21 RU)
for each Cisco Nexus 7010 system.
Figure
3-2.
OL-23069-06

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nexus 7009Nexus 7018Nexus 7010

Table of Contents