Notification Appliance/Auxiliary Power Circuits; 1: Conventional Notification Appliance; Class B Notification Wiring - Honeywell 6808 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Control Panel Installation
A number of programmable options are available for customizing telephone lines. These options are described in Section 9.6.

4.13 Notification Appliance/Auxiliary Power Circuits

NOTE: These circuits are considered regulated unless used for releasing type service, in which case they are considered special applications.
Four outputs are built-in to the 6808 FACP which can be programmed to be used as NACs (Class A or Class B) or as Aux power.
This section of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary
power.
4.13.1 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for Class A and Class B configurations.

Class B Notification Wiring

You must use an appliance from the list of compatible appliances in Appendix A at the back of this manual.
To install a Class B notification appliance circuit:
1.
Wire Class B Notification appliances as shown in Figure 4.40.
2.
Configure the circuit through programming (see Section 9.5).
48
Supervised
Figure 4.39 Connection of Telephone Lines
Figure 4.40 Class B Notification Appliance Circuit Wiring
EOL 4.7 k
Alarm Polarity Shown
Notification Wiring
Supervised
Power Limited
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017