Sia - Panel Communicator - Honeywell 6808 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Reporting
Fire Alarm-Point
Fire Alarm-Point
Expander Trouble
Auto Test
Battery Trouble-Panel 32
Battery Trouble-Expander
18
SLC Loop Shorted
Program Begin Panel
ID=32
Program Begin Panel ID=
22
AC Power Loss - Panel 22
Fire Trouble
Fire Trouble
Fire Trouble-Nac
Fire Trouble-Nac
11.3 SIA – Panel Communicator:
(Differences/additional features are underlined)
Events are sent to the Central Station Receiver as a fixed length string:
The event format is:
EEPPMMZZZZ
Where
EE
Event code (2 characters)
PP
Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM
Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Module information)
ZZZZ Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit
information)
1.
The Event field will contain 10 digits including the 2 digit event code (EE), 2 digit panel ID (PP), 2 digit Module Number (MM)
and a 4 digit Event Parameter (ZZZZ).
2.
Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent information. In that case
the field will contain zeros.
3.
The account number is sent using an account block that is separate from the event block.
4.
Multiple events can be sent within a single event block. Events are separated by a "/" character.
5.
Event parameter can be a Zone, Point or Circuit Number.
6.
"pi" modifier event is not used.
7.
Panel can be set to report by either Point or Zone.
138
Event
Point
n/a
Point
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Point
n/a
Zone
n/a
Point
n/a
Zone
n/a
Table 11.4: SIA- Panels - PI Modifier Reporting Examples
01
n/a
123
EE-ZZ /EE-
ZZZ
33
n/a
203
EE-ZZ /EE-
ZZZ
11
n/a
n/a
EE-ZZ
n/a
n/a
n/a
EE-Z
98
n/a
n/a
EE-ZZ
18
n/a
n/a
EE-ZZ
44
n/a
n/a
EE-ZZ
n/a
n/a
n/a
EE-Z
n/a
n/a
n/a
EE-Z
98
n/a
n/a
EE-Z
97
n/a
200
EE-ZZ /EE-
ZZZ
97
01
n/a
EE-Z
98
n/a
Nac
EE-ZZ /EE-
Circuit 7
Z
98
n/a
Nac
EE-ZZZ
Circuit 7
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
pi01/FA123
pi11/FA203
ET11
RP0
YT98
YT18
ET44
LB0
LB0
AT0
pi97/FT200
FT1
pi98/FT7
Z=Pt. #
FT400
ZZZ=OPG#