1: Single Interlock Zone Releasing - Honeywell 6808 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

System Operation
Detectors must be installed at 0.7 times the linear spacing as described in NFPA 72, Chapter 2.
10.6.1 Single Interlock Zone Releasing
A single interlock zone utilizes a minimum of two addressable detectors, and a designated manual release switch.
Conditions Required for an Pre-Alert Output Activation
If any single addressable detector is activated, the "Pre-Alert" output will activate. This alerts the user that the initial stages required for
a release condition are present. (Also refer to Table 10.3.)
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the "Alarm" and the "Release" outputs will activate and the
"Pre-Alarm" output will deactivate. (Also refer to Table 10.3.)
1st Addressable Detector
2nd Addressable Detector
Manual Release Station
124
Figure 10.6 Wiring Configuration for Solenoid
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Inputs
Table 10.3 Single Interlock Zone Operation
Important!
Important!
Output Results
X
X
X
X
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017