When using T-taps, the total length of all taps and the main bus must be met in addition to the maximum distance requirements for the
various wire gauges
7.5.2 Wiring SLC in Class A Configuration
Figure 7.3 illustrates how to wire the SLC loop for Class A installations.
NOTE: Style 6 does not use short circuit isolator devices
NOTE: Style 7 requires an isolator module as the first device on the in and the out loop
NOTE: No t-taps allowed on class A SLC loops
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Figure 7.2 Calculating Wire Run Length for T-tap
Figure 7.3 Class A SLC Configuration
SK, SD and SWIFT™Wireless SLC Device Installation