Programming
To edit a zone, follow these steps:
1.
Enter the installer code.
2.
Press 7 for Program Menu.
3.
Press 2 to enter zone menu.
4.
Press 1 to edit a zone.
5.
Enter the zone number, then press ENTER.

Edit Zone Name

6.
Press 1 to edit the selected zone name. You can use words to display a descriptive name for a zone.
NOTE: See Appendix B for editing names.

Edit Zone Properties

Zone properties consist of, alarm delay characteristics, and heat detector sensitivity.
1.
Do steps 1 through 5 of Section 9.3.1.
2.
Press 2 to edit the properties of the selected zone.
Alarm Delay Characteristics
The programmed zone type is provided for user reference only. To modify the zone type use the HFSS Honeywell Fire Software Suite.
Table 9.1 list the delay choices and a description of each.
Type of Delay
1-Count
2-Count
Alarm Verification
PAS - Positive Alarm
Sequence
SNGL ILOCK
100
Figure 9.2 Editing Zone Properties
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device
of any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is
considered the most typical operation and is the default for all zones.
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order
for the zone to report an alarm. Switches of type manual pull, Detector Switches, water flow, Aux1 and
Aux2 are an exception; they will cause an alarm when only one switch is in alarm.
When a single detector is in alarm in a 2-Count zone, the system enters a prealarm condition. In a
prealarm condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has
occurred. If the zone has been mapped to an output group for the prealarm event, the output group will
activate. The prealarm will not be reported to the central station.
Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by
resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has completed,
the detector will go into alarm. If the detector is no longer in alarm, no report will go to the central station.
The alarm verification sequence is ignored if the zone is already in alarm.
This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds,
giving on-site personnel a chance to investigate the alarm. If the acknowledge switch is not activated
within 15 seconds, an alarm occurs automatically.
If this option is enabled for a zone, the zone will respond to an alarm condition as follows:
The zone will not go into alarm for 15 seconds to allow an on-site operator to activate the
acknowledge switch.
• If the operator does not press the acknowledge switch within 15 seconds, the zone will go into alarm.
• If the operator presses the acknowledge switch within 15 seconds, a 180-second time-frame will begin
counting down. This time-frame allows the operator to investigate the cause of the alarm.
• If the operator performs a reset within 180 seconds, the alarm will not occur.
• If the operator does not perform a reset within 180 seconds, an alarm will occur automatically.
• The P.A.S. feature will be overridden if another alarm occurs.
See Section 10.6.1 for single interlock releasing operation.
Table 9.1 Alarm Delay Characteristics
Detection type also
selected from this
screen (see Table 9.1).
Description
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017