2: Requirements For Central Station Fire Alarm Systems; 3: Requirements For Local Protected Fire Alarm Systems; 4: Requirements For Remote Station Protected Fire Alarm Systems; 5: Requirements For The Installation Of Carbon Monoxide (Co) Detection And Warning Equipment, Nfpa 720 - Honeywell 6808 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

2.
Use the addressable smoke detectors specified in Section 7 of this manual and or conventional detectors listed in the compatibility
chart. (See Appendix A.)
3.
Use UL listed notification appliances compatible with the 6808 from those specified in the Appendix A at the back of this manual.
4.
A full system checkout must be performed any time the panel is programmed.
Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 3 hours. For UL certified installations this
number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications
whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
The system allows the Alarm Verification time to be set from 60 to 250 seconds. For UL certified installations the setting must be a
minimum of 60 seconds.
The system allows the Auto-resound time to be set to 24 or 4 hours. For UL certified installations that are utilizing SWIFT devices,
the value must be set to 4 hours
Call forwarding shall not be used.
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be
used.
P.A.S feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm Systems
1.
Use both phone lines. Enable phone line monitors for both lines.
2.
You must program a phone number and a test time so that the 6808 shall automatically initiate and complete a test signal
transmission sequence to its associated receiver at least once every 6 hrs.
3.
The AC Loss Hours option must be set from 1-3 hours.
4.
If using wired Ethernet or cellular, you must program the corresponding account/subscriber ID and a test time so that the FACP
shall automatically initiate a test signal transmission sequence to its associated receiver at least every 6 hrs.
2.2.3 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used. Minimum system requirements are one Silent Knight addressable
initiating device.
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems
Minimum system requirements are one Honeywell Silent Knight addressable initiating device and either a 5220, Keltron 3158 or the
built-in Digital Alarm Communicator Transmitter (DACT).
1.
Do not exceed the current load restrictions shown in Section 3.7.2.
2.
The AC Loss Hours option must be set from 1-3 hours.
2.2.5 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station.
2.2.6 NFPA Requirements
The following is the minimum configuration to meet the NFPA requirements.
Model/Module
006808CB
068080
RA-100BD
SK-NIC
SK-FML/ -FSL
7644
5220
Keltron 3158
Cell-Mod/Cell-Cab-
SK
Y = YES, N = NO, O = OPTIONAL
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Description
Local
Enclosure
Y
Motherboard
Y
4 x20 display
Y
Network card
O
Fiber module
O
Pol Rev device
N
City tie, Pol. Rev
N
Device
Rev Pol Module
N
Cellular
N
transmitter
NFPA Requirements for 6808
Table 2.2
Agency Listings, Approvals, and Requirements
Remote
Releasing
Auxiliary
Station
Y
Y
Y
Y
Y
Y
Y
Y
Y
O
O
O
O
O
O
N
Y
N
N
Y
Y
N
Y
Y
N
Y
N
Central
Emergency
Station
Signaling
Y
Y
Y
Y
Y
Y
O
O
O
O
N
N
N
N
N
N
Y
N
15