3.5 Wiring Specifications

Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms.
To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel. Instead,
separate the wiring as follows:
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as
possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the
sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3.1 for an example.
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Label
Group
Individual
AC INPUT
B
Earth
W
TROUBLE
NC
COM
NO
RELAY 1
NC
COM
NO
RELAY 2
NC
COM
NO
NAC1*
+
NAC2*
+
NAC3*
+
NAC4*
+
EXT. Comm
B
Cellular
A
Connection
S+
S-
Data Network
Table 3.1 Terminal Descriptions and Electrical Specifications
High voltage
SLC loops
POTS reporting
input/output
Notification circuits
SBUS
Relay circuits
Description
AC input (hot)
Earth Ground
AC input (neutral)
Normally closed relay contact
Common terminal
Normally open relay contact
Normally closed relay contact
Common terminal
Normally open relay contact
Normally closed relay contact
Common terminal
Normally open relay contact
Notification Appliance
Circuit/Auxiliary power
Notification Appliance
Circuit/Auxiliary power
Notification Appliance
Circuit/Auxiliary power
Notification Appliance
Circuit/Auxiliary power
Cellular Transmitter
Used for SK-NIC
AC power terminal
SLC In/Out Terminals
Phone line circuits, Ring Tip Telco, Phone
Terminals
NAC 1-4
SBUS Out Terminals, Cellular communication
Trouble, Relay 1, Relay 2 Terminals
Before You Begin Installing
Rating
Voltage
Current
120 VAC, 60 Hz
3.3 A
N/A
N/A
120 VAC, 60 Hz
3.3 A
24 VDC
2.5 A, resistive
24 VDC
2.5 A, resistive
24 VDC
2.5 A, resistive
24 VDC
3.0 Amp NAC or Aux
power
24 VDC
3.0 Amp NAC or Aux
power
24 VDC
3.0 Amp NAC or Aux
power
24 VDC
3.0 Amp NAC or Aux
power
input
55 mA, 95 mA
24 VDC
21 mA