The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex
wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4.11 for location of the set screws).

Flush Mounting

This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.
Flush Mounting with an Electrical Box
The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-gang, and double-gang. If an electrical box is
used, the box must be 1-3/8" back from the face of the wall to accommodate the annunciator. Studs used with an electrical box must be
two by fours (or larger).
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Holes for surface mounting.
Holes for inserting
wires for flush mounting
(located in all corners).
Set screw location.
Loosen set screws to remove bezel
when disassembling annunciator.
Figure 4.11 Annunciator Back Box and Bezel Details
Examples of Electrical Box Use
wall
studs
annunciator
back box
(outline)
electrical
box
Figure 4.12 Placement of Electrical Box for Flush Mounting
Knockout holes
Stand-off
(throughout)
Screw for placement
of mounting wires
(top and bottom).
Electrical Box Placement
Annunciator
back box
When flush-mounting using an
electrical box, the box must be
1-3/8" from face of wall.
Electrical box applications require
2 by 4 construction minimum.
Control Panel Installation
Sheet rock
1-3/8"
Electrical Box
Sheet rock