9.5 Point

You may need to change characteristics of individual input points (detectors and switches) even after using JumpStart
ming. This section explains how to change options for: type of point, latching/non-latching, silenceable/non-silenceable, zone assign-
ment (input points), detector accessory base options, group assignment (output points), and point name.
9.5.1 Point Programming for SLC
To program points on SLC, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.6 Quick Reference Table for available choices.
Then press ENTER.
5.
Select S for sensor or M for module. (SK Only)
6.
Enter the number of the point you wish to edit, then press ENTER.
7.
Select the type of device by pressing the up or down arrow key. Refer to Table 9-3 under the column heading "Type Selection" for a
list of choices
Type Selection
UNUSED
SD DETECTOR
SD SUP DET
SK DETECTOR
SK SUP
DETECTOR
CO SMOKE
DETECTOR
W-DETECTOR
W-SUP-DET
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Function
Latching Option
PHOTO
ION
HEAT
PHOTO DUCT
PHOTO
ION
Latching
HEAT
Non Latching
PHOTO DUCT
ION DUCT
PHOTO
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
PHOTO
PHOTO
ION
HEAT
PHOTO DUCT
Latching
Non Latching
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
ALRM CO/
ALRM FIRE
SUP CO/
ALRM FIRE
ALRM CO/
SUP FIRE
Latching
SUP CO/
SUP FIRE
Non Latching
Photo
Photo-Heat
Heat
Latching
Same as W-Detector
Non Latching
Table 9.2 SLC Point Programming
Comments
Supervisory can be latching or non-latching.
Detectors programmed as Supervisory can be latching or non-
latching.
Wireless photoelectric detector
Wireless heat detector
Programming
®
Autoprogram-
103