How To Check Network Card Status; Fault Finding; High Errors - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions

How to check Network Card status

Using the Menu On/Off -> [Info] -> [Status] -> [Card] and enter the network card address in this
case it is '4'. The display will confirm:
¨
the address of the network card
¨
the address of network controller
¨
and a set of condition codes
Card 4 Is OK Fault 0:Disable 0:Warning 0
Address (0) Version 4.06
Node 3
Controller 1 Baud Rate 38400
Condition 0 0 0 0 0 0 2 1 198 199
Side 2
Side 1
Side 2
Side 1
Parity/
Parity/
CRC
CRC
Framing
Framing
error
error
Current
message
1 error = count of
errors
10 but every 1sec
1 error =
the counter is
count of
decremented by 1
100
Errors
meaning
Parity
Parity is incorrect, data corrupted.
Framing
8- bit transmitted incorrectly and the data line does not return to
logic 1 at the end of the transmission.
CRC
Cyclic redundancy code. When a message consisting of a number
of 8 bit transmissions is sent, a calculation is carried out to check
that data corruption has not occurred.
Time out
Where an 8 bit transmission block is not fully received, the
error
network card will time out ready to receive the next message. A
time out error will also be generated for each parity/ framing error.
88
5/7/06
Side 2
Side 1
UART
End
type
communicating
1 or 2
0-Rockwell
Timing
1-Phillips
errors
2-Phillips SMT
Only appears
on Controller
Errors
meaning
Freeblock
Free memory blocks available to temporarily store messages
waiting to be processed. The maximum number = 199, although it
may drop as low as 175 - 180 on a highly populated network. A
lower value may indicate a high error value and will require
rectification.

Fault Finding

¨
The communication path in a secure network will alternate between end 1 (side 1) and
end 2 (side 2) every minute.
¨
The network will be non secure until the last panel is connected and powered-up.

High errors

¨
Check cable lengths and type used.
Freeblock
¨
Check wiring, connections and earthing arrangements. Check the network cable is
correctly earthed to the equipment.
Check
software
¨
Replace network card at point of failure, where required.
¨
Check the addresses and baud rates of the network cards of all the networked panels.
¨
It may be necessary to investigate and:
look at the noise voltage between conductors, screen and earth.
"
Always reset the Network Card first when rechecking for errors, using
[Test/Eng] -> [Card] ->[Reset] -> Network Card 4.
On completion of the above the networked system may now be configured for network operation,
for master sectors and global controls to be actioned as per site requirements.