Commissioning instructions

Auxiliary Relays

The two Auxiliary relays in the control panel are defaulted to operate on:
a Sectored fire event the Auxiliary relay 1 and
a fault event the Auxiliary relay 2.
¨
the Auxiliary relays can be configured for normally-open or normally-closed
operation
¨
the Auxiliary relays may be configured to be operated with:
a Fault
a Warning
any combination of Sectored Fire events
or any of the above combination
¨
It is possible to delay the operation of each relay by up to 10 minutes after the first
FIRE event. The accuracy of the delay is 0 - 4 seconds
¨
The relay will operate immediately for fault and warning events.
154

Radio Device

A Plexus radio device is bound to a LRT and can be configured using the Plexus Commissioning
tool in a similar manner to any other system device, however see the following note.
"
It is important to note that a Radio sensor device do not have multiple STATES
and therefore a radio sensor device cannot operate with Timeslot, like for example a
S-Quad sensor where the sensor STATE can be switched at pre defined times of a day.
Prior to commissioning radio devices using the commissioning tool ensure they are all
pre-commissioned using the Plexus Pre-commissioning tool.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.