Mains Supply; External Printer; How To Configure The Monitored Input; How To Configure The Buttons U1 And U2 - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions

Mains supply

Dedicated mains supply
from consumer unit
230V ac
5A Unswitched fused
spur unit
PANEL
FS3 3.15A(T)
Mains fuse
&
Ensure the mains supply cable enters the panel through a dedicated
cable entry point.
"
These fire alarm system products are NOT designed to be powered from an IT
Power system.
All mains powered equipment must be earthed. Mains supply to any fire alarm control and
indicating equipment must be via a dedicated unswitched 5A fused spur unit, which should be
clearly labelled FIRE ALARM - DO NOT SWITCH OFF.
A disconnect device must be provided to disconnect both poles and must have a minimum gap of
3mm. The 'disconnect device' should be available as part of the building installation and must be
easily accessible after installation is complete.
50
N E
L
P2
DANGER
&
Hazardous voltage remains after operation of a protection fuse. Take
appropriate action to guard against the risk of equipment having exposed live
mains supply.
Audio LEDs
The Audio LEDs on the ACC card are associated with Audio Loop 1 and
Audio Loop 2, to indicate when the audio is active. When the background
AUDIO LOOP 1
music, centrally stored message held on the message store card (these
include attention tones), emergency microphone and/or PA microphone
BGM MPG MIC PA
is active, then the respective LED is lit.
AUDIO LOOP 2
Under normal condition the MIC LED is lit, this is a 'park' position.
When the emergency microphone is used and on pressing the PTT button the attention tone will
sound, so the MPG LED is lit briefly before the MIC LED is lit again for live announcements.
PSU Indicators
As for VIGILON Compact, see page 40.
PSU link
As for VIGILON Compact, see page 41.

External printer

As for VIGILON Compact, see page 43.

How to configure the monitored input

As for VIGILON Compact, see page 41.

How to configure the buttons U1 and U2

As for VIGILON Compact, see page 43.

How to configure LEDs CB253 and CB254 (Legacy)

As for VIGILON Compact, see page 43.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.