Commissioning instructions

Mains supply

Dedicated mains supply
from consumer unit
230V ac
5A Unswitched fused
spur unit
PANEL
N E
L
P2
FS3 3.15A(T)
Mains fuse
&
Ensure the mains supply cable enters the panel enclosure through a
dedicated cable entry point.
"
These fire alarm system products are NOT designed to be powered from an IT
Power system.
All mains powered equipment must be earthed. Mains supply to any fire alarm control and
indicating equipment must be via a dedicated unswitched 5A fused spur unit, which should be
clearly labelled FIRE ALARM - DO NOT SWITCH OFF.
A 'disconnect device' must be provided to disconnect both poles and must have a minimum gap of
3mm. The device should be available as part of the building installation and must be easily
accessible after installation is complete.
&
Hazardous voltage remains after operation of a protection fuse. Take
appropriate action to guard against the risk of equipment having exposed live
mains supply.
40
DANGER
PSU Indicators
P3
43V
FS6
1A P7
BAT1
-
Y1 Y2 G1
Description
Y1
(yellow LED)
Normal condition
(no faults in the system)
Mains out of limit
24VDC failure only
Battery 1 failure only
Battery 1 and 24VDC failure
43VDC failure only
fast flash
No power to PSU
Earth fault only
On
"
On initial power-up all three PSU LEDs will switch ON for approximately
1 second.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
PSU BOARD
Y1 Y2 G1
+
Y2
G1
(yellow LED)
(green LED)
fast flash
slow flash
fast flash
fast flash
slow flash
fast flash
slow flash
fast flash
fast flash
On