Sectors

* I/O LINES MAY BE SECTORED INDIVIDUALLY FOR STANDARD MAINS POWERED
INTERFACE UNITS AND NOT FOR LOOP POWERED INTERFACE UNITS.
DEVICES
ASSIGN
& I/O LINES
WITHIN A
SECTOR
*
DELAY
ACTION
BLOCK
SIGNAL
1
SIGNAL
2
COMMAND
ACTION
BUILD
SIGNAL
3
NO
ACTION
SECTOR
ACTION
That has just
come into fire
¨
There can be up to 32 sectors per loop
¨
a Sector is a collection of devices on the same loop having a common action
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
SIGNAL
1
SIGNAL
2
SIGNAL
32 SECTORS
3
PER LOOP
NOTE : SECTORS 29 TO
NO
ACTION
32 ARE FOR
SPECIAL USE
SECTOR
SIGNAL
1
SETUP THE SECTOR
TO DE-ENERGIZE ON
SIGNAL
2
SILENCE ALARMS
OR RESET
BUTTON
SIGNAL
3
NO
ACTION
DEFAULT: SIGNAL-1 = ALERT
NOTE : A SECTOR CAN ONLY ACTION OTHER LINKS
SIGNAL-2 = EVACUATE
IF THE FIRE IS AT A DEVICE ASSIGNED TO THAT SECTOR.
SIGNAL-3 = CONTINUAL
NOTE: VOICE ALARM ZONES ARE PUSH BUTTON
CONTROLS ON THE MAIN PANEL.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
¨
a Sector that is actioned ON will activate its alarm
devices, such as interface outputs, S Cubed, S-Quad and
DAU devices.
a sector can be configured to give one of three signals
Signal 1 Alert (priority 3)
Signal 2 Evacuate (priority 2)
Signal 3 Continuous (priority 1).
COMMAND
BUILD
¨
Sectors 1-28 operate automatically with 'Sound Alarms'
and 'Silence Alarms' buttons
DELAY
¨
a Sector (any one of 1-28) that is configured for NO
BLOCK
action on 'Sound Alarms' button being pressed will be
silenced on operation of the 'Reset' button
TRIGGER
AUX
¨
RELAYS
ACTION
the Sectors 29-32 are independent of the 'Sound Alarms'
button and are primarily used for the control of plant
ACTION
equipment. However, the Sectors 29-30 can be
configured to normal sector operation
SECTOR
ACTION
¨
sensors, call points and interface inputs may be assigned
ASSIGN
to more than one Sector
VOICE ALARM
ZONES
¨
a loop powered interface is assigned to a Sector and
ASSIGN
consequently the inputs and outputs lines of
MASTER
will be assigned to the same Sector
SECTOR
¨
S4 devices having alarm sounder and interface outputs are
restricted to one Sector only
¨
for Voice alarm panel there can be up to 10 Voice Alarm
Zones
¨
Voice alarm zone are push button switches on the Voice
alarm control panel that can be assigned to Sectors
¨
any normal Sector (1-28) can be assigned to any Voice
alarm zone (1-10).
that interface
143