Message Action List - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Message Action list

The messages displayed at the control panel, network node or loop repeat panels are given here in an alphanumerical order to provide guidance:
¨
on a 'fault message'
¨
the likely meaning of the message
¨
along with suggestions on what initial actions may be taken to rectify the problem.
"
Only the messages that are applicable will appear on the display of the control panel, network node or loop repeat panels. Additionally the display will identify the panel
where the event was first detected.
¨
The term device was previously referred to as outstation.
Message
associated with..
MCC / MCB
A spurious FIRQ at
card x
(main control card/board)
MCC / MCB
A spurious IRQ at
(main control card/board)
card x
MCC / MCB
A spurious NMI at
card x
(main control card/board)
A spurious SWI2 at
MCC / MCB
(main control card/board)
card x
MCC / MCB
A spurious SWI3
(main control card/board)
at card x
Access fault at
Any Card
card x
Network Card or
ACIA Failed at
MCC / MCB
card x
Alarms silenced
MCC / MCB
(main control card/board)
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
There is glitch on the MCC hardware that appears on
the backplane / MCB.
There is glitch on the MCC / MCB hardware.
There is glitch on the MCC / MCB hardware.
There is glitch on the MCC hardware.
There is glitch on the MCC / MCB hardware.
Card cannot talk to the MCC / MCB local controller.
Communication chip failure or the FABs and SABs are
corrupt.
Silence alarms button has been pressed.
..possible action
Clear and ignore single occurrence.
Clear and ignore single occurrence.
Clear and ignore single occurrence.
Clear and ignore single occurrence.
Clear and ignore single occurrence.
Replace card if the fault keeps reoccurring.
Could also be caused by excessive network
messages. Investigate message passing.
Reset the card and replace if it fault keeps
reoccurring.
-