Fire Protection Equipment (Fpe) - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions

Fire Protection Equipment (FPE)

¨
There can more than one Interface configured FPE application in a Vigilon System.
FPE Interface can be a MV Interface unit S4-34411, but can be also be a S4-34415 or S4-34420.
Other interface units can also be configured as FPE, these include S4-34440-02, S4-34440-12, S4-34401 and
S4-34404.
¨
a FPE Interface device is automatically placed in plant Sector 32 (as default) and is unaffected by operation of
SOUND ALARMS control
¨
a FPE Interface device may be Enabled or Disabled from the panel menus select:
Menu On/Off button to select: [Control] -> [Enable] / [Disable] -> <etc> -> <etc> -> <etc> -[FPE] -> [E].
Vigilon loop
Sensor
Alarm
device
H
MCP
INTERFACE #
MORE THAN ONE INTERFACE #
DEVICE IN A VIGILON SYSTEM
CAN BE SET UP TO OPERATE AS
SETUP
FIRE PROTECTION EQUIPMENT (FPE)
as FPE
INTERFACE #
MORE THAN ONE INTERFACE #
DEVICE IN A VIGILON SYSTEM
CAN BE SET UP TO OPERATE AS
SETUP
as FPE
FIRE PROTECTION EQUIPMENT (FPE)
# - Can be a MV Interface unit S4-34411 or S4-34415
156
ENABLED OR
DISABLED
FPE
ACTION
FPE
ACTION
Duct mounted fire Dampers,
Fixed fire fighting system,
Sprinkler or water spray system
Smoke and Heat control system or
Hold open device for fire / smoke doors
Duct mounted fire Dampers,
Fixed fire fighting system,
Sprinkler or water spray system
Smoke and Heat control system or
Hold open device for fire / smoke doors
"
Where a FPE interface is required to be disabled
then use the FPE device disablement option.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.