Commissioning instructions
Controls applicable for Vigilon Compact VA panel only - (legacy product)
Pressing one or more of the 10 buttons selects the local Voice Alarm Zone(s) of the local
n
system to which emergency or auxiliary messages, or emergency microphone is to be
announced. The two LEDs beneath flash alternately to show the Voice Alarm Zone has
been selected.
(green and red)
On selecting the required emergency or auxiliary message only one of these LEDs changes
to steady or flashing indication determined by the type of audio to be outputted to the
selected Voice Alarm Zones. The left LED indicates auxiliary message selection while the
right LED indicates emergency message selection.
(Green)
Pressing the 'All Zones' button allows quick selection of all Voice Alarm Zones
simultaneously. The accompanying LED gives a steady indication when the button is
All Zones
pressed. Note all the VA Zones that have been setup in your system will give a flashing
indication and those not setup will give no indications.
Clear Zones
Pressing 'Clear Zones' button will clear selected Voice Alarm Zones, also when auxiliary
messages are being announced pressing 'Clear Zones' will silence the announcements.
Speak Now
When 'Speak Now' light is illuminated the system is ready to allow live speech
announcement to selected Voice Alarm Zones via the Emergency microphone.
(green)
The indicator is lit following the selection of Voice Alarm Zones and on pressing the Press to
Speak Now
Talk (PTT) button on the Emergency microphone.
If the 'Press to Talk' button is released the 'Speak Now' indicator will flash and switch off
after 20seconds duration or immediately switch off on pressing the Clear Zone button.
(green)
When the 'VA Activated' LED is illuminated it indicates the voice announcements are being
VA Activated
made or emergency microphone is in use for speech announcement to Voice Alarms Zones.
(red)
Auxiliary messages
When illuminated the system is announcing auxiliary message n to the selected Voice Alarm
Zones.
(green)
The indicator is lit following the selection of Voice Alarm Zone(s) and on pressing the
required Auxiliary message button.
n
Emergency messages
When illuminated the system is announcing emergency message n to the selected Voice
Alarm Zones.
(Red)
The indicator is steady or flashing determined by the type of emergency message being
n
announced to Voice Alarm Zones.
22
Voice Alarm Zones
1
2
3
6
7
8
All Zones
Clear Zones
VA Activated
Speak Now
Auxiliary messages
Emergency messages
1
TEST START
ALERT
TEST END
EVACUATE