Honeywell Vigilon 4 loop Generic Commissioning Instructions page 124

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions
Message
associated with..
Device
Device power
too high/
restored too low
/restored number x on
loop y
LPC
Device Replaced is
faulty number x on
(loop processor card)
Loop y
LPC
Device Replaced
number x loop y
(loop processor card)
Radio (Plexus) Device
Device Returned
Device soft address;
Device
SAFE:
number x on
loop y
MCC / MCB
Disables Cleared
(main control card/board)
Duplicate SAFE
Device
Address error:
number x on loop y
Power supply
Earth Fault/ Fault
Cleared
LPC
Earth Fault at Card n
(2Km Loop Processor Card)
Loop n: 0v resistance
is xxR, L is y
Loop n: Earth is aaa,
bbb (99)
MCC / MCB
Enabled Aux relay x
(main control card/board)
Disabled Aux relay x
124
meaning..
Internal power rail of mains powered interface unit has
a value of rectified DC equal to or greater than 32V
(high) / less than 30V (restored)
DC equal to or less than 24V (low) / greater than 26V
(restored)
Tx fault re-finding device.
The replaced device is now communicating with the
panel.
Radio device has been returned to it's base
Device primary address does not match SAFE address.
All disablements have been removed from the panel.
Two devices on a loop have the same SAFE address.
The ADC value to earth of the 8V regulator:
is equal to or greater than 5 (for a +ve fault)
or less than 3 ( for a -ve fault).
There is an earth fault present before allocation.
Note: An Earth fault post allocation is indicated as
Earth fault.
The auxiliary relay has been enabled or disabled
automatically or manually.
..possible action
Replace the device
Check connections to device / base and also
device type etc.
-
The moved Radio (Plexus) Device has been
returned to its original installed position.
Check loop configuration.
-
Change one of the SAFE address.
A clear indication is normally given when ADC
is equal to 64.
Use the Loop Diagnostic Tool to diagnose the
earth fault condition and rectify it.
If necessary, manually enable/disable the
auxiliary relays using the [control] menu.