Honeywell Vigilon 4 loop Generic Commissioning Instructions page 118

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions
Message
associated with..
MCC / MCB
Alarms sounded
(main control card/board)
Alarms Verified
MCC / MCB
(main control card/board)
LPC
Alarm Zone Disabled /
Enabled at card x
(loop processor card)
LPC
Allocation : Double
Allocated card x
(loop processor card)
number y on loop z
LPC
Allocation : Hw fault
card x number y on
(loop processor card)
loop z
Allocation : Map
LPC
error card x number y
(loop processor card)
on loop z
LPC
Allocation
: memory
Overflow at card x
(loop processor card)
number y on loop z
LPC
Allocation : not
ready at card x
(loop processor card)
LPC
Allocation : OK at
Card n : Allocated x
(loop processor card)
Allocation started
LPC
from end 2 at card x
(loop processor card)
LPC
Allocation : Too many
card x number y on
(loop processor card)
loop z
Allocation : Tx fault
LPC
card x number y on
(loop processor card)
loop z
118
meaning..
Sound alarms button has been pressed.
Alarms verify button has been pressed.
-
Two devices are given the same address. Loop breaker
(relay contacts) are fused 'micro welded' together
(closed) or there is a bad connection.
Loop breaker relay has not closed or serial line End-2
is faulty or relay is stuck i.e. closed. The device may
not be correctly fitted.
Loop wiring is incorrect, eg a sub loop may have been
wired on a spur.
Loop processor has run out of memory during
allocation / when starting a loop.
An attempt to allocate a loop when it is already
allocating.
The loop circuit has been successfully allocated.
No devices found on End-1 or End 1 of the loop is
open circuit.
Allocated more than 200 devices or the device is
restricted for use with the particular software version.
Invalid reply from the device.
..possible action
-
-
Check the device wiring. The device may be
faulty, replace if required.
Check the device wiring. The device may be
faulty, replace if required.
Check and rewire if necessary. This fault can
also be device failure.
Software error or more likely a faulty RAM
chip.
Wait and if it takes longer than 10 minutes then
reset the loop card.
-
Check the wiring to the first device or last
device on the loop.
Replace incompatible devices used on other
systems ie:32000 or SMS device found in
system.
Check the device. Also check cable routing and
length (measure resistance and capacitance of
cable).
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.