Fire Alarm Routing Equipment (Fare) - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Fire Alarm Routing Equipment (FARE)

¨
There can be one FARE Interface per Vigilon System.
FARE Interface can be a LV Interface unit S4-34420, but can also be a S4-34450.
Other interface units can be configured FARE, these include S4-34440-02, S4-34440-12, S4-34401 and S4-34404.
¨
a FARE Interface device is automatically placed in plant Sector 32 (as default) and is unaffected by operation of SOUND
ALARMS control
¨
a FARE Interface device may be switched ON or OFF from the panel menus select:
Menu On/Off button to select [Control] -> <etc> -> [FARE] -> [ON] or [Off] -> [E]
¨
a FARE device may be Enabled or Disabled from the panel menus, select:
Menu On/Off button to select: [Control] -> [Enable] / [Disable] -> <etc> -> <etc> -> <etc> -[FARE] -> [E]
Vigilon loop
Sensor
Alarm
device
SWITCH
H
ON / OFF
MCP
ONE LV INTERFACE #
SETUP
as FARE
DEVICE IN A VIGILON SYSTEM
CAN BE SET UP TO OPERATE AS
FIRE ALARM ROUTING
EQUIPMENT (FARE)
LV INTERFACE #
# - LV Interface unit (S4-34420)
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
ENABLED OR
DISABLED
FARE
ACTION
Confirmation
Vigilon 4/6 loops & Compact (VA) panels & network nodes
"
disabled then use the FARE device disablement
option.
ALARM RECEIVING CENTRE
Where a FARE interface is required to be
155