Honeywell Vigilon 4 loop Generic Commissioning Instructions page 136

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions
Message
associated with..
MCC / MCB
System Printer fitted
(main control card/board)
at card x number y
loop z
System Printer Lost
MCC / MCB (Printer option)
at card x number y on
loop z
MCC / MCB
System Restarted
/Started
(main control card/board)
MCC / MCB
System stopped
(main control card/board)
Any Card
Task stuck
at card x
LPC
Test set found /
removed at card x
(loop processor card)
Too many errors
Device
number x on loop y
Network Card
Too many errors x at
Card y
Network
Two controller at
card x
MCC / MCB / DAC
Two master has the
same address at
card x
Any Card
Unable to claim
buffers at
card x
LPC
Unrecoverable Tx
fault number x loop y
(loop processor card)
136
meaning..
A 80 column serial printer is fitted to the panel.
TBA
Link on back plane restored.
Backplane link moved causing the system to stop.
Software error.
Remote allocation unit has been found connected to the
system.
More than 15 errors from a device in 34 hours.
Up to 6 consecutive communication errors.
There are two network controllers.
Two PCs have been given the same address.
System too busy
More than 3 consecutive reply errors
..possible action
-
TBA
-
The link should not be normally accessed.
Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
Disconnection of the test set will bring about a
removed message.
Check the loop wiring to the device.
Check wiring and cable screen. There may be
faults with the installation.
One network controller will automatically shut
down.
Each PC must have a unique address.
Wait or reset card if stuck, record in the log
book
Check the device connections and replace if
necessary.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.